| Outdoor air supplies are mandatory in many North American building codes. Too bad they don't work. | ![]() |
The
Wood Heat Organization: Answers to your questions about burning wood for heat and enjoyment. |
The Outdoor Air Myth ExposedOutdoor combustion air was a good idea . . . until it was studiedBuilding codes all over North America require that fireplaces, and in some cases wood stoves, be provided with a source of combustion air from outdoors. This mostly takes the form of a four inch hole in an outside wall with a duct attached running to the stove or fireplace, connected either directly to the firebox or to a location where it can be heated by the fire before entering the room. Sometimes the air is just dumped somewhere in the room. There seem to be three theories behind this outdoor air supply, depending on who is doing the explaining. The first is to replace the air sucked out of the house by the wood burner, based on the idea that houses are airtight and the wood burner will use up all the oxygen. The second is to reduce the risk of smoking into the room, even when the room is depressurized by a big fan like a kitchen range exhaust. The third is to save energy by using outdoor air rather than indoor air that has already been heated. But it doesn't matter which theory you pick; they're all misguided. It turns out that the most consistently reliable place to take combustion air from is the room where the appliance is installed. Forget about outdoor air supplies as a way to make wood stoves and fireplaces work better or be more efficient. If your local building code forces you to install outdoor air, you will have no choice, but be aware that it will not reliably improve the performance of your wood burning appliance or result in higher efficiency of the system. The outdoor combustion air myth got started about forty years ago when safety and construction standards were written for mobile homes. Because they were small and factory-built, it was believed that mobile homes were air tight. As a result, all wood, oil and gas furnaces, stoves and fireplaces had to get their air from outdoors. Because these air supplies were invariably routed straight down into the ventilated crawl space under the mobile home, they didn't cause too many problems, so it was assumed that they actually worked. In the 1980s, when large exhaust systems – like downdraft kitchen range exhausts – began to cause spillage from fireplaces in reasonably tight houses, a consensus quickly formed around the idea of bringing combustion air from outdoors, just as had been done in mobile homes for decades. Such certainty existed among housing technologists and regulatory authorities on the issue of outdoor combustion air that it was made mandatory in most building codes. Unfortunately, the decision to enforce mandatory outdoor air rules was made before research was done to investigate how they actually work. The benefit of providing a supply of outdoor air to the appliance is not supported by research results. Laboratory and field reports have revealed that providing outdoor air is not a simple or effective cure for spillage, and that some designs could create a fire hazard. Two forms of outdoor air supply have been used: passive make-up type air supplies and direct-to-combustion chamber air supplies. Passive make-up air suppliesA passive make-up type air supply is one that is not connected directly to the fireplace or stove combustion chamber. Since it is connected only to the house environment and not to the appliance, it flows air into a house only when the pressure inside is lower than the pressure outdoors, since air only flows to zones of lower pressure. Passive air supplies don't make wood burners work better, they just make the house leakier.
It is useful to keep in mind a key
physical principle: The real problem with the passive make-up air strategy is that it does not reliably supply combustion air, nor does it reliably reduce combustion spillage. Under favorable conditions it may tip the balance of driving and adverse pressures in favor of successful venting. This is why some fireplace specialists have reported performance improvements after the installation of a passive supply. However, it is also possible for a passive supply to cause spillage if air is drawn out of the house into a low pressure zone caused by wind effects. A remedial strategy that only works sometimes, and that may make the problem worse, is not a good strategy. A passive make-up air supply is really nothing more than another uncontrolled leak in the house envelope. A leaky house envelope is no guarantee of successful venting. Direct-to-combustion chamber outdoor air suppliesOutdoor air supplies connected directly to the stove or fireplace combustion chamber may seem like a good idea and it was once believed that a direct supply would isolate the combustion appliance from room pressure variations. However, two key findings from the research into outdoor air supplies serve as cautions against the widespread use of direct combustion air supplies.
Evidence of wind-induced reversals in combustion air ducts is becoming more common now that so many systems have been installed. When servicing systems with direct outdoor combustion air ducts, look for soot or staining inside the duct. If there is any evidence of reversal, disconnect the duct and plug the hole in the house envelope. It has been suggested that a direct combustion air supply to a woodburning appliance would eliminate its air consumption impact on other chimney vented combustion equipment in the building. However, when their doors are closed, wood heating appliances exhaust comparatively little air from the dwelling. Wood stoves with gasketed doors consume in the range of 10 - 25 cubic feet per minute of air, which is a tiny amount of air, much less than an oil furnace, for example. Since the air consumption of a wood stove is so low, the risk of reversal of a ducted combustion air supply outweighs any advantage gained by bringing air from outdoors. An open fireplace, in contrast, can exhaust such a large volume of air that it could affect the operation of, for example, a conventional gas-fired furnace or water heater. But direct combustion air supplies cannot effectively be connected to a fireplace without doors because insufficient pressure difference is created to drive the flow. In other words, there is no simple way to provide the large volume of air used by a fireplace by supplying it from outdoors, except perhaps by opening a window. There may be circumstances in which a direct outdoor air supply is considered necessary. If it is decided to supply combustion air directly to a firebox, it should be done with full awareness that spillage is still likely if the room becomes seriously depressurized and, for safety reasons, steps should be taken to control temperatures on combustibles adjacent to the air supply duct in case wind effects lead to a flow reversal.
A fireplace vented by natural draft needs a reliable and unrestricted supply of combustion air. Since passive outdoor air supplies in reasonable sizes are ineffective and since direct combustion air supplies are unreliable and potentially dangerous, other options must be considered. The most obvious alternative is to take combustion air from inside the building. Ideally, a fireplace operating on natural draft takes its combustion air from a neutral pressure environment so that the air supply is steady and consistent. Perfection would be an air supply provided at neutral pressure and with no resistance to flow. Fireplaces consume combustion air in response to the amount of chimney draft produced by the heat of their own flue gases. A stove or fireplace will be fussy to start and likely to spill when it tries to get its combustion air from a seriously depressurized building. The extent of building depressurization is deducted from potential chimney draft, like this: theoretical draft - depressurization = net draft Building depressurization competes directly with chimney draft. If the chimney wins the competition, the flow direction is up (successful venting); if the fan causing the depressurization wins, the flow is down (spillage or backdrafting). The advantage of taking combustion air directly from the room in which the fireplace is installed is that the building envelope moderates the effect of wind on the air supply by damping out wind-induced pressure fluctuations. The pressure inside the house will still be affected by wind to some extent, but the flow resistance offered by the envelope tends to remove the peaks and valleys of high and low pressure caused by wind gusts. The main disadvantage of taking air from inside the house is that the pressure environment can be adversely affected by powered exhausts. However, depressurization caused by powered exhaust flows is predictable and manageable, unlike the more random and unpredictable effects of wind on outdoor air supplies. The worst-case indoor air pressure environment can be measured using the house pressure test procedure, and can be controlled either by limiting exhaust flows or by installing a powered make-up air system. In general, therefore, fireplaces that are vented by natural chimney draft should draw the air for combustion from the room in which they are located. Where necessary the indoor air pressure should be controlled to minimize depressurization. |